parameter | |
---|---|
CTRL/1/tuitsp | setpoint for discharge temperature (0,1 degree) |
CTRL/1/klpsp | setpoint runtime motor for positioning discharge grill (time ) |
CTRL/1/flwsp | setpoint for fan speed (0-6) |
CTRL/1/ena | Enable bitmask: 0=output 1 1=output 2 2=cool 3=heat 4=on |
CTRL/1/afzsp | setpoint for exhaust fan (for BEM always 0) |
CTRL/1/tinpv | unit inlet sensor (0,1 degree) |
CTRL/1/tuitpv | unit discharge temperature (0,1 degree) |
CTRL/1/err | error mask unit. (some are overruled by control panel or BEM) |
CTRL/1/stat | unit state mask: bit 0=OK (not used) bit 1=err(not used) bit 2=hsp button state bit 3=input 1 bit 4=input 2 |
CTRL/1/foul | filter fouling (%) ; not used anymore |
CTRL/1/toptpv | unit (outdoor) temperature sensor (0,1 degree) |
CTRL/1/uflws | input voltage terminal X370 (used for PIR sensor or filter pressure sensor) (0,01V) |
CTRL/1/flwpress | actual pressure difference (0,1 Pa) |
CTRL/1/vlvoff | water valve positioning set point unit off (%) |
CTRL/1/cvlv | actual cooling valve positioning (%) |
CTRL/1/hvlv | actual heating valve positioning (%) |