SDO:drivers:daikin_itc

Read/Write indoor-unit values from „Daikin Intelligent Touch Controller“ (DCS601C51) (old version).

This requires the Web- License (DCS004A51) for software version < 3.05 or HTTP- License (DCS007A51) for newer software versions.

settings

setting values description
debug
consumption_software
address
task_Poll
task_Write
task_PollProperties
task_PollConnectionStatus
merge_rw

abstracts

  • IUs
  • Daikin_IndoorUnit

URI structure

Indoor-Unit-States

/<driver_name>/iu_states/<unit_id>/<field>
  • <unit_id> - 0..127
  • <field> one of
    • EnableDisableTemp
    • FanDirection
    • FilterSign
    • MalfunctionCode
    • Status
    • FanSpeed
    • OperationMode
    • OnOff
    • SetTemp
<field> read/write values meaning
EnableDisableTemp rw
FanDirection rw 0-7 0..6 - 0..90°
7 - swing
FilterSign rw 1,2
MalfunctionCode ro 2-char ASCII see: Daikin Error-Codes
Status ro 0..2
FanSpeed rw low, high, high2
OperationMode rw heat, cool, fan, dry
OnOff rw 0,1
SetTemp rw loat>

ITC-State

/<driver_name>/_online
/<driver_name>/_state/lastError
/<driver_name>/_state/lastResponseTime
doc/sdo/drivers/daikin_itc.txt · Zuletzt geändert: 2013.11.25 - 20:42 von 127.0.0.1
 