SDO:drivers:daikin_itc
Read/Write indoor-unit values from „Daikin Intelligent Touch Controller“ (DCS601C51) (old version).
This requires the Web- License (DCS004A51) for software version < 3.05 or HTTP- License (DCS007A51) for newer software versions.
settings
| setting | values | description |
| debug | | |
| consumption_software | | |
| address | | |
| task_Poll | | |
| task_Write | | |
| task_PollProperties | | |
| task_PollConnectionStatus | | |
| merge_rw | | |
abstracts
URI structure
Indoor-Unit-States
/<driver_name>/iu_states/<unit_id>/<field>
<unit_id> - 0..127
<field> one of
EnableDisableTemp
FanDirection
FilterSign
MalfunctionCode
Status
FanSpeed
OperationMode
OnOff
SetTemp
| <field> | read/write | values | meaning |
| EnableDisableTemp | rw | | |
| FanDirection | rw | 0-7 | 0..6 - 0..90°
7 - swing |
| FilterSign | rw | 1,2 | |
| MalfunctionCode | ro | 2-char ASCII | see: Daikin Error-Codes |
| Status | ro | 0..2 | |
| FanSpeed | rw | low, high, high2 | |
| OperationMode | rw | heat, cool, fan, dry | |
| OnOff | rw | 0,1 | |
| SetTemp | rw | loat> | |
ITC-State
/<driver_name>/_online
/<driver_name>/_state/lastError
/<driver_name>/_state/lastResponseTime